HEAT TRANSFER FLUIDS    

 YOUR HEAT TRANSFER NEEDS ARE OUR ONLY CONCERN
"The Exception To The Rule"
MultiTherm FF-1 ® Flushing Fluid
The Logical First Step in Heat Transfer System Start-Up!
 
 
Temperature Density Thermal Conductivity Specific Heat Viscosity Vapor Pressure
°F °C lb/ft2 lb/gal kg/l Btu/hr-ft-°F W/m-°C Btu/lb-°F kJ/kg-°C Centistoke Centisposise lb/ft-hr mm Hg PSI
0 -18 58.17 7.78 0.932 0.0753 0.1303 0.39 1.63 1515 1412 3416 -
-
50 10 57.05 7.63 0.914 0.0742 0.1284 0.42 1.76 110.7 101.2 244.8 - -
100 38 55.99 7.49 0.897 0.0730 0.1264 0.45 1.88 22.9 20.5 49.59 0.00005 0.000001
150 66 54.86 7.33 0.879 0.0718 0.1243 0.48 2.01 8.27 7.27 17.59 0.00047 0.000009
200 93 53.74 7.18 0.861 0.0707 0.1223 0.51 2.14 4.10 3.53 8.54 0.00320 0.000062
250 121 52.62 7.03 0.843 0.0696 0.1205 0.54 2.26 2.45 2.07 5.01 0.01600 0.000309
300 149 51.49 6.88 0.825 0.0684 0.1184 0.57 2.39 1.66 1.37 3.31 0.06700 0.001296
350 177 50.37 6.73 0.807 0.0673 0.1165 0.60 2.51 1.21 0.98 2.37 0.23000 0.004447
400 204 49.25 6.58 0.789 0.0660 0.1142 0.63 2.64 0.93 0.73 1.77 0.69000 0.013342
450 232 48.12 6.43 0.771 0.0650 0.1125 0.65 2.72 0.74 0.57 1.38 1.84000 0.035580
500 260 46.94 6.28 0.752 0.0638 0.1104 0.67 2.81 0.61 0.46 1.11 4.41000 0.085275


Warranty: MultiTherm® warrants that MultiTherm FF-1® conforms to the data set forth in this brochure. We present this information in good faith, but because we cannot control or anticipate the many different conditions under which our information and product may be used, no other warranty, expressed or implied, is given.